KARYA ILMIAH

Pengarang
Lanto Mohamad Kamil Amali
Subjek
- Teknik
Abstrak
The problem in this study were: (1) how the intensity of pollution sector in the region polluted insulator, (2) how polluted insulator surface conductivity parent substations in cach region, (3) how to profile an appropriate insulators for intensity of pollution sector in the region. To solve this problem pollutant sampling conducted on ceramic insulators on the channel milestone substantion switchyard each region at two different points, namely at the top of the insulator and the bottom fin insulators. The results showed the intensity of pollution for every region of substantion at a value of NSDD categorized insoluble low-level pollutant. Maximum leakage current value obtained by GI. Makale 4.73 mA, GI. Sungguminasa 4.47 mA, GI. Tello 4.60 mA, GI. Long Tallo Ma and GI. Pangkep 4.87 mA. Keyword : Insulator, Pollutant, ESDD, NSDD
Penerbit
Jurusan Teknik Elektro Fakultas Teknik Universitas Tadulako
Kontributor
-
Terbit
2011
Tipe Material
ARTIKEL
Right
-
Berkas ini telah didownload sebanyak 1017 kali
Download