SCIENTIFIC WORK

Author
Ade Irawaty Tolago
Subject
- Teknik
Abstract
Disturbance on the transmission line can cause disruption of normal flow of a stream, in the transmission line of the most common disorders are short circuit. Distance relay are used as security for the transmission line because of its ability to quickly eliminate interference. In this research, symmetrical components method is used in to analyzing the single-phase short circuit current and two phase – ground in SUTT 150 kV Gorontalo Transmission System. The results were obtained, single-phase short circuit at most 1098,11 Ampere and the smallest is 497,67 Ampere and two phase – ground at most ? I?_b = 1026,91 Ampere and ? I?_c = 650,86 and the smallest is ? I?_b = 442,63 Ampere and ? I?_c = 337,55 Ampere, while the calculation results setting distance relay it is appropriate to avoid the reach selectivity setting exceeding 80% and avoid looping and time settings on zona1 = 0 s zona2 = 0,4 s and zona3 = 0,8 s according to the impedance value of the secondary Z_es 1 < Z_es 2 as well as on Z_es 2 < Z_es 3. Keyword: Transmission, Symmetrical Components, Short circuit, Setting Distace Relay
Publisher
AKSARA JURNAL ILMU PENDIDIKAN NONFORMAL MARET 2016
Contributor
ADE IRAWATY TOLAGO, TAUFIQ YUSUF ISMAIL. LAODE MUH TASLAN
Publish
2016
Material Type
LAPORAN PENELITIAN
Right
ISSN :2407-8018 VOLUME 02/NOMOR 02
This files has been downloaded 521 times
Download